Toshiba HWS-1402XWHM3-E, HWS-802XWHT6-E Function code table, Item, Details, First shipment

Models: HWS-1402XWHT9-E HWS-1402XWHM3-E HWS-1402XWHT6-E HWS-1501CSHM3-E(-UK) HWS-1402H-E HWS-2101CSHM3-E(-UK) HWS-3001CSHM3-E(-UK) HWS-802XWHM3-E HWS-802H-E HWS-802XWHT6-E

1 168
Download 168 pages 43.83 Kb
Page 108
Image 108

Function code table

FC

Item

 

 

Details

First shipment

 

 

 

 

 

 

01

Water heat exchanger capacity

0012: 802XWH**-E

 

 

Depends on type

 

 

0017: 1402XWH**-E

 

 

 

 

 

 

 

 

 

 

02

Cooling/Non-cooling switching

0000: Cooling

 

0001: No cooling

0001: No cooling

 

 

 

 

 

 

 

 

07

Hot water HP operation mode upper time limit

0000:

0 mins

-

0120: 120 mins

0030:

30 mins

 

 

 

 

 

 

 

 

08

Hot Water Boost operation time

0003:

30 mins

-

0018: 180 mins

0006:

60 mins

 

 

 

 

 

 

 

 

09

Hot Water Boost set temperature

0040:

40°C

-

0080: 80°C

0075:

75°C

 

 

 

 

 

 

 

 

0A

Anti bacteria set temperature

0070:

70°C

-

0080: 80°C

0075:

75°C

 

 

 

 

 

 

 

 

0B

Anti bacteria holding time

0000:

0 mins

-

0060: 60 mins

0030:

30 mins

 

 

 

 

 

 

 

 

0C

Mixing valve drive time

0003:

30 secs

-

0024: 240 secs

0006:

60 secs

 

 

 

 

 

 

18

Upper limit of cooling set temperature

0018: 18°C

-

0030: 30°C

0025: 25°C

 

 

 

 

 

 

19

Lower limit of cooling set temperature

0010: 10°C

-

0018: 18°C

0010: 10°C

 

 

 

 

 

 

1A

Upper limit of heating (ZONE1) set temperature

0037: 37°C

-

0055: 55°C

0055: 55°C

 

 

 

 

 

 

1B

Lower limit of heating (ZONE1) set temperature

0020: 20°C

-

0037: 37°C

0020: 20°C

 

 

 

 

 

 

1C

Upper limit of heating (ZONE2) set temperature

0037: 37°C

-

0055: 55°C

0055: 55°C

 

 

 

 

 

 

1D

Lower limit of heating (ZONE2) set temperature

0020: 20°C

-

0037: 37°C

0020: 20°C

 

 

 

 

 

 

1E

Upper limit of hot water set temperature

0060: 60°C

-

0080: 80°C

0075: 75°C

 

 

 

 

 

 

1F

Lower limit of hot water set temperature

0040: 40°C

-

0060: 60°C

0040: 40°C

 

 

 

 

 

 

20

Hot water HP start temperature

0020: 20°C

-

0045: 45°C

0038: 38°C

 

 

 

 

 

 

21

Hot water HP stop temperature

0040: 40°C

-

0050: 50°C

0045: 45°C

 

 

 

 

 

 

22

Priority mode Hot water supply/Heating switching

-0020: -20°C

-

0020: 20°C

0000: 0°C

 

temperature

 

 

 

 

 

 

 

 

 

 

 

 

23

Priority mode Boiler/Heat pump switching temperature

-0020: -20°C

-

0020: 20°C

-0010: -10°C

 

 

 

 

 

 

24

Outside air temperature for hot water temperature

-0020: -20°C

-

0010: 10°C

0000: 0°C

 

correction start

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25

Hot water temperature correction value

0000:

0K

-

0015: 15K

0003:

3K

 

 

 

 

 

 

 

 

26

Night set back change temperature range

0003:

3K

-

0020: 20K

0005:

5K

 

 

 

 

 

 

 

27

Set temperature shift with heating Auto

-0005: -5K

-

0005: 5K

0000:

0K

 

 

 

 

 

 

29

Outside air temperature T1 temperature

-0015: -15°C

-

0000: 0°C

-0010: -10°C

 

 

 

 

 

 

2B

Outside air temperature T3 temperature

0000: 0°C

-

0015: 15°C

0010: 10°C

 

 

 

 

 

 

2C

Set temperature A with outside air temperature of -

0020: 20°C

-

0055: 55°C

0040: 40°C

 

20°C

 

 

 

 

 

 

 

 

 

 

 

 

2D

Set temperature B with outside air temperature of T1

0020: 20°C

-

0055: 55°C

0035: 35°C

 

 

 

 

 

 

2E

Set temperature C with outside air temperature of 0°C

0020: 20°C

-

0055: 55°C

0030: 30°C

 

 

 

 

 

 

2F

Set temperature D with outside air temperature of T3

0020: 20°C

-

0055: 55°C

0025: 25°C

 

 

 

 

 

 

30

Set temperature E with outside air temperature of 20°C

0020: 20°C

-

0055: 55°C

0020: 20°C

 

 

 

 

 

 

31

Zone2 ratio with Zone1 as Auto

0000: 0%

-

0100: 100%

0080: 80°C

 

 

 

 

 

 

33

Heater control down time

0000: 5 mins

 

0001: 10 mins

0001: 10 mins

 

 

0002: 15 mins

 

0003: 20 mins

 

 

 

 

 

 

 

 

34

Heater control up time

0000: 10 mins

 

0001: 20 mins

0000: 10 mins

 

 

0002: 30 mins

 

0003: 40 mins

 

 

 

 

 

 

 

 

3A

Frost protection function Yes/No

0000: No

 

0001: Yes

0001: Yes

 

 

 

 

 

 

3B

Frost protection set temperature

0010: 10°C

-

0020: 20°C

0015: 15°C

 

 

 

 

 

 

3C

Water 2-way energization (logical reverse) control

0000: No

 

0001: Yes (Reverse)

0000: No

 

 

 

 

 

 

3E

Heating HP/Boiler priority switching when using boiler

0000: Priority on HP

 

0001: Priority on boiler

0000: Priority on HP

 

 

 

 

 

 

 

 

107