[A09] Error Overheat prevention thermostat failure (Hot water supply/Heating operation)

Start

Water cycle contains water

No

 

Yes

 

Flow switch is normal

No

 

Yes

 

At normal temperature,

No

overheat preventive thermostat

 

is normal

 

Yes

 

Put water into water circuit (Recommended: 1 - 2 Bar)

Manual background Replace flow switch

Replace heater unit exchanger air vent valve

Replace water heat exchange control board or overheat preventive thermostat failure

*Replace water heat exchange control board or overheat preventive thermostat failure: After the control board is replaced, if the same operation repeats, the overheat preventive thermostat is determined as defective (does not operate at 75°C).