Toshiba HWS-1402XWHT6-E, HWS-802XWHT6-E, HWS-802H-E, HWS-802XWHM3-E, HWS-3001CSHM3-E(-UK) Check code

Models: HWS-1402XWHT9-E HWS-1402XWHM3-E HWS-1402XWHT6-E HWS-1501CSHM3-E(-UK) HWS-1402H-E HWS-2101CSHM3-E(-UK) HWS-3001CSHM3-E(-UK) HWS-802XWHM3-E HWS-802H-E HWS-802XWHT6-E

1 168
Download 168 pages 43.83 Kb
Page 97
Image 97
Manual background

Check code

Outdoor LED

Check and Action procedure

indication

(No specific description indicates outdoor unit parts.)

 

 

 

 

 

[P19]

<Indication 1> <Indication 2>

[4-way valve invert failure]

 

 

 

4-way valve operates normally.

No

 

 

(Check piping temperature at the

 

 

 

 

 

time of cooling/heating operation)

 

 

 

Yes

 

Temperature sensor check

TE sensor CN601

TS sensor CN600

Hydro TWO sensor

If defective, repair or replace it

4-way valve coil resistance

No

 

Replace 4-way coil

is 1.3 to 1.6 k .

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor control

board operation

NG

Check outdoor board

check (See below)

 

If defective, replace it

 

 

OK

 

 

 

 

 

 

 

 

 

 

 

 

 

4-way valve check

 

 

 

 

If defective, replace it

 

 

 

 

 

 

 

 

 

Outdoor control board operation check direction (Self-hold valve)

1)With the dip switch SW804 set as in the table below, pressing SW801 for approx. 1 second can check the operation of switching to cooling cycle or to heating cycle.

The board are energized for 10 seconds.

Take more than a minute for the next check because the parts (coil, resistance R700) generate large heat.(This does not apply when no coil is connected.)

2)After the check, set all the SW804 dip switches to OFF.

Switching to cooling cycle

Switching to heating cycle

SW804

SW801

CN701

SW804

SW801

CN701

ON

Manual backgroundManual backgroundManual backgroundManual background1 2 3 4

Press

 

 

 

 

 

4

 

 

 

 

 

 

3

 

 

 

 

2

ON

 

 

 

1

 

 

 

 

 

 

 

 

Press

180DCV or higher

180DCV or higher

Note: Check with a tester

With an analog tester: If a tester shows 180DCV or higher, the board is good.

With digital tester:

Although values shown has some range, if its maximum value is

 

180DCV or higher, the board is good.

96