Toshiba HWS-1402XWHM3-E, HWS-802XWHT6-E, HWS-802H-E, HWS-802XWHM3-E, HWS-3001CSHM3-E(-UK) Check code

Models: HWS-1402XWHT9-E HWS-1402XWHM3-E HWS-1402XWHT6-E HWS-1501CSHM3-E(-UK) HWS-1402H-E HWS-2101CSHM3-E(-UK) HWS-3001CSHM3-E(-UK) HWS-802XWHM3-E HWS-802H-E HWS-802XWHT6-E

1 168
Download 168 pages 43.83 Kb
Page 98
Image 98
Manual background

Check code

Outdoor LED

 

Check and Action procedure

indication

 

(No specific description indicates outdoor unit parts.)

 

 

 

 

 

 

 

 

 

 

 

 

 

[P20]

<Indication 1> <Indication 2>

[Hi pressure protection operation]

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

Service valve is fully opened.

 

 

Open fully service valve

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating season

 

 

 

 

 

 

 

 

 

Reset the power source and perform

Heating operation

 

 

 

a trail operation according to the season.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling season

 

 

 

 

 

 

 

 

Cooling operation

 

 

 

 

 

 

 

 

Outdoor TL sensor is normal.

No

 

 

 

 

 

 

 

Replace sensor

 

 

 

 

 

 

 

 

 

 

 

(Measure resistance)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor fan is free from crack

No

Check outdoor fan

 

 

 

 

 

 

 

 

 

 

or looseness.

 

 

If defective, replace or tighten it

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor fan operates normally.

No

Check the same item as

 

 

 

 

 

 

 

 

 

 

Yes

 

 

those for [P22] abnormality

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Something prevents outdoor unit

Yes

 

 

 

 

 

 

 

heat exchange

Remove the disturbing

 

 

 

 

 

 

 

 

 

 

- Clogged heat exchanger

 

 

element

 

 

 

 

- short circuit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

Check for refrigerant overcharged, clogged cycle, pipe break, abnormal overload, etc. If defective, repair defective portion

Something prevents heat

 

 

exchange of hydro unit.

Yes

 

Remove the

- Clogged filter

 

 

disturbing element

- Clogged heat exchanger

 

 

 

- Short circuit

 

 

No

 

 

Check for refrigerant overcharged, clogged cycle, pipe break, abnormal overload, etc. If defective, repair defective portion

97

Page 98
Image 98
Toshiba HWS-1402XWHM3-E, HWS-802XWHT6-E, HWS-802H-E, HWS-802XWHM3-E, HWS-3001CSHM3-E(-UK), HWS-2101CSHM3-E(-UK) Check code