Check code

Outdoor LED

 

 

 

 

 

 

Check and Action procedure

 

 

indication

 

 

 

(No specific description indicates outdoor unit parts.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[H02]

<Indication 1> <Indication 2>

[Compressor lock]

 

 

 

 

 

 

 

 

 

 

Power voltage is normal.

 

No

 

 

 

 

 

 

 

 

 

Improve power line

 

 

 

 

 

230ACV ± 23V

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wiring connection

 

is normal.

No

 

 

 

 

 

 

 

Check and correct

 

 

 

 

 

Compressor lead

 

(board side,

 

 

 

 

 

 

 

 

 

 

 

wiring connection

 

 

 

 

 

compressor side)

 

reactor, power lead

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor is normal.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant stays inside.

 

 

No

 

Lock compressor and

 

 

 

 

 

 

 

 

 

 

replace it.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pulse motor valve operates

 

No

 

TE, TS sensor pulse

 

 

 

 

 

 

 

 

motor valve check

 

 

 

 

 

 

normally.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If defective, replace

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check outdoor board

 

 

 

 

 

 

 

 

 

 

 

 

If defective, replace it

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[H04]

<Indication 1> <Indication 2>

[Case thermostat operation]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN609 connector and case

No

 

Correct connector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

thermostat is normal.

 

 

 

 

Replace case thermostat

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If case thermostat

 

is short circuited,

No

 

Check outdoor board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cooling and heating

 

can operate.

 

 

 

 

If defective, replace it

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No gas leakage.

 

 

 

 

No

 

Correct defective portion

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enough Refrigerant.

 

 

 

 

Re-charge refrigerant

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Service valve is fully opened.

No

 

Open fully service valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pulse motor valve is normal.

No

 

Correct defective portion

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace defective parts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check for piping collapse and break.

 

 

 

 

 

 

 

 

 

 

 

If defective, repair or replace it.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[L10]

<Indication 1> <Indication 2>

[Model not set] Only when service board is used

 

 

Cut jumper line by following the instruction comes with the service board package

92

Page 93
Image 93
Toshiba HWS-3001CSHM3-E(-UK) Is normal Check and correct, Board side Wiring connection, Compressor is normal Yes