2) Control at the time of heating heater operation

Item

 

 

 

 

 

 

 

Operation flow and applicable data, etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8-3.

 

 

2) Control at the time of heating heater operation

 

 

 

 

 

 

Hydro Unit

 

 

Controlled Object: Backup heater, Booster heater

 

 

 

 

 

 

Control

 

 

 

The backup heater control starts when 13 minutes has passed after the heating heat pump operation started.

 

 

 

 

The backup heater control increases, decreases, or maintains the number of heaters every 10 minutes (FC)

 

 

 

 

depending on the difference between the heating set temperature (TSC_F) and the heater outlet temperature

 

 

 

 

(THO). Note that when the heating set temperature (TSC_F) is reached, the unit stops energizing the heater.

 

 

 

 

THO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70

E zone

Abnormality detection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Diff : 2K

 

 

 

 

 

 

 

 

 

 

 

D zone

 

 

 

 

 

 

 

 

 

 

 

 

 

Heater off

 

 

 

 

 

 

 

 

 

TSC_F-0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heater output down every

 

 

 

 

 

 

 

 

 

 

 

C zone

 

 

 

 

 

 

 

 

 

 

 

 

 

5, 10, 15, or 20 minutes

 

 

 

 

 

 

 

 

TSC_F-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Diff : 2K

 

 

 

 

 

 

 

 

 

 

 

B zone

 

 

 

 

 

 

 

 

 

 

 

 

 

KEEP

 

 

 

 

 

 

 

 

 

TSC_F-4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Diff : 2K

 

 

 

 

 

 

 

 

 

 

 

A zone

 

 

 

 

 

 

 

 

 

 

 

 

 

Heater output up every

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10, 20, 30, or 40 minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Status

 

 

Heater ON / OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heater 1

 

Backup heater 3 kW = ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heater 2

 

Backup heater 9 kW = ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heater 3

 

Heater 2 + Booster heater

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The single-phase model of 3 kW has the backup heater 1 only.

 

 

 

 

 

 

 

The three-phase model of 6 kW has heater 1+2 of 6 kW.

 

 

 

 

 

 

 

 

Contact point output only is available for booster heater.

 

 

 

 

 

 

 

Related FC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FC No.

 

 

 

 

Setting item

 

 

Default

 

Setting available range

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

Hot water supply heat pump start temperature

 

38°C

 

 

20-45°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21

 

Hot water supply heat pump stop temperature

 

45°C

 

 

40-50°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

33

 

Heater control of down time

 

 

1:10 mins

 

0:5 mins

2:15 mins

3:20 mins

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

34

 

Heater control of up time

 

 

0:10 mins

 

1:20 mins

2:30 mins

3: 40 mins

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-3) Heater control at the time of defrosting

 

 

 

 

 

THO

 

 

 

 

 

• Object to be controlled: Backup heater

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When a defrosting operation starts during the heating heat

 

 

TSC_F

 

 

 

 

 

pump operation, the unit energizes a backup heater (3 kW)

 

 

Heater off

 

 

 

 

TSC_F-β(β=2)

 

 

 

according to the heater outlet temperature sensor (THO) and

Heater 1

 

 

 

 

 

 

 

 

 

the set temperature (TSC_F) as follows.

 

 

 

TSC_F-α(α=4)

 

 

 

 

 

 

Heater 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1)When the heater outlet temperature sensor (THO) drops to the temperature of 2°C below the set temperature

 

Status

Heater ON / OFF

Defrosting ends according to the usual heater control.

 

 

Heater 1

Backup heater 3 kW = ON

2-4) Forcible heater energization

To prevent freeze, the unit energizes or stops energizing a backup heater (3 kW) regardless of the unit status, not operated or in operation.

• Object to be controlled: Backup heater

1)Energization start condition: TWO < 4 or TWI < 4 or THO < 4

2)Energization stop condition: TWO Manual background 5 and TWI Manual background 5 and THO Manual background 5 Defrosting ends according to the usual heater control.

2-5) No heater operation

According to the DP_SW11 setting, the unit switches the energize/ not energize for the hot water cylinder, backup heater, and booster. For details, see 10-1.

51

Page 52
Image 52
Toshiba HWS-802XWHM3-E, HWS-802XWHT6-E, HWS-802H-E, HWS-3001CSHM3-E(-UK) Control at the time of heating heater operation