Toshiba HWS-802H-E, HWS-802XWHT6-E, HWS-802XWHM3-E, HWS-3001CSHM3-E(-UK), HWS-2101CSHM3-E(-UK)

Models: HWS-1402XWHT9-E HWS-1402XWHM3-E HWS-1402XWHT6-E HWS-1501CSHM3-E(-UK) HWS-1402H-E HWS-2101CSHM3-E(-UK) HWS-3001CSHM3-E(-UK) HWS-802XWHM3-E HWS-802H-E HWS-802XWHT6-E

1 168
Download 168 pages 43.83 Kb
Page 81
Image 81
Manual background

[A08] Error Lo pressure sensor lowering operation failure (Cooling/Defrosting operation)

Start

 

 

 

 

 

No

 

 

 

 

 

 

 

Flow switch is

normal

 

 

 

 

 

 

Replace flow switch

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remove sufficiently

 

 

Excess air

 

 

 

 

 

 

excess air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

Secure water

 

 

Waste stuck inside

 

 

noise comes from

 

 

 

Remove waste

 

 

circulation amount

 

 

water circuit

 

inside pump

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12 M or longer water

 

Place buffer tank and

 

 

 

 

 

 

 

 

 

 

 

pipe to a branch,

 

the second pump

Chattering

Yes

 

 

 

 

or 5 or less branches

 

 

 

 

 

 

 

 

Circulation flow

 

 

 

 

 

noise comes from

 

 

 

 

 

 

 

 

 

 

 

 

flow switch

 

 

shortage

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

Continued

 

 

 

 

 

 

 

 

 

operation at low outside

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

Raise set temperature

temperature and at 15°C or lower

(Cooling overload operation)

 

 

 

set temperature

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

Defrosting

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

Defrost outdoor unit

takes 15 mins or longer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

where frost remains

(Frost remains)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

Lo pressure sensor

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace lo pressure sensor

 

 

 

 

 

 

 

 

 

is normal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace water heat

 

 

 

 

 

 

 

 

 

exchange control board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

Page 81
Image 81
Toshiba HWS-802H-E, HWS-802XWHT6-E, HWS-802XWHM3-E, HWS-3001CSHM3-E(-UK), HWS-2101CSHM3-E(-UK), HWS-1402H-E, HWS-1402XWHT6-E