Toshiba HWS-1402H-E, HWS-802XWHT6-E, HWS-802H-E Item, Operation flow and applicable data, etc

Models: HWS-1402XWHT9-E HWS-1402XWHM3-E HWS-1402XWHT6-E HWS-1501CSHM3-E(-UK) HWS-1402H-E HWS-2101CSHM3-E(-UK) HWS-3001CSHM3-E(-UK) HWS-802XWHM3-E HWS-802H-E HWS-802XWHT6-E

1 168
Download 168 pages 43.83 Kb
Page 55
Image 55
8-1)Piping freeze prevention control 1

Item

Operation flow and applicable data, etc.

 

 

8-3.

7) Automatic restart control

Hydro Unit

The unit records operation information before a power outage and retrieves the information after the power is on again

Control

to restart automatically the operation with the information.

7-1) Operation during remote controller

The operation status before a power outage automatically restarts after the power is on again. (The merit functions are also enabled)

Approximately 6 hours or more after a power outage

The operation status before a power outage automatically restarts after the power is on again. But the merit functions (Night Set Back, Anti Bacteria) are disabled.

The remote controller time displays "--:--". (The merit functions are disabled)

7-2) Operation during forcible automatic operation

A forcible automatic operation is performed when the power is on again after a power outage.

7-3) Operation during defrosting operation

When the power is on again after a power outage, the usual operation restarts. Note: The operation details recorded before a power outage

Operation mode: Hot water supply, Heating, Cooling, Hot water supply + Heating, Hot water supply + Cooling

Set temperature: Hot water set temperature, Heating set temperature, Cooling set temperature

Merit function:

Hot water supply operation (Anti Bacteria)

 

Heating operation (Night Set Back)

8)Piping freeze prevention control

This control operates when the power is on regardless the remote controller setting ON or OFF.

To prevent frost bursting of the water piping for hot water supply and heating, the unit flows water with the circulation pump when the temperature sensor value falls below a certain temperature.

8-1)Piping freeze prevention control 1

1)Start condition: TWO < 4°C or THWI < 4°C.or THO < 4°C

2)End condition: TWO Manual background 5°C and TWI Manual background 5°C and THO Manual background 5°C

3)-1 How to operate (circulation pump)

When the circulation pump is not in operation, if the sensor detects the freeze prevention control start temperature, the unit operate the circulation pump.

During a freeze prevention operation, a heat pump operation does not start.

When neither [HOT WATER] nor [ZONE1, 2] is in operation, if the end condition is not met when 3 minutes has passed after an operation starts, the unit performs the operation in 3)-2 to prevent freeze.

3)-2 How to operate (circulation pump + backup heater)

When neither [HOT WATER] nor [ZONE1, 2] is in operation, if the end condition is not met when 3 minutes has passed after an operation starts.

End condition: TWO Manual background 5°C and TWI Manual background 5°C and THO Manual background 5°C

Heating with the set temperature 55°C operates.

3)-3 Abnormal stop

If a freeze prevention operation continues for 30 minutes and does not meet the end condition, the operation stops as abnormal stop. (Remote controller check code: A5)

54

Page 55
Image 55
Toshiba HWS-1402H-E, HWS-802XWHT6-E Item, Operation flow and applicable data, etc, 8-1Pipingfreeze prevention control