[F07] Error TL sensor failure

Start

 

 

 

 

 

 

 

TL sensor

No

 

Correct TL sensor

connector (CN604) is

 

connection

connected

 

 

 

Yes

 

 

TL sensor

No

 

Replace TL sensor

resistance characteristic

(See characteristic table on page 101)

is normal

 

 

Yes

Replace water heat exchange control board

[F08] Error TO sensor failure

Start

 

 

 

 

 

 

 

TO sensor

No

 

Correct TO sensor

connector (CN602) is

 

connection

 

connected

 

 

 

Yes

 

 

TO sensor

No

 

Replace TO sensor

resistance characteristic

 

(See characteristic table on page 101)

is normal

 

 

Yes

Replace water heat exchange control board

[F10] Error TWI sensor failure

Start

 

 

 

 

 

 

TWI sensor

No

 

 

connector (CN205) is

 

 

 

 

connected

 

 

 

 

Yes

 

 

Correct TWI sensor connection

TWI sensor

No

 

Replace TWI sensor

characteristic is normal

 

 

(See characteristic table on page 101)

Yes

 

 

 

 

 

 

Replace water heat exchange control board

 

 

 

 

 

 

86