Toshiba HWS-1402H-E, HWS-802XWHT6-E, HWS-802H-E Fig Prevention of oxidation during brazing

Models: HWS-1402XWHT9-E HWS-1402XWHM3-E HWS-1402XWHT6-E HWS-1501CSHM3-E(-UK) HWS-1402H-E HWS-2101CSHM3-E(-UK) HWS-3001CSHM3-E(-UK) HWS-802XWHM3-E HWS-802H-E HWS-802XWHT6-E

1 168
Download 168 pages 43.83 Kb
Page 15
Image 15
Fig 2-5-1

5)Use the reducing valve to adjust the nitrogen gas flow speed to 0.05 m3/hour or 0.02 MPa (0.2 kgf/cm2).

6)After the steps above, keep the nitrogen gas flowing until the pipe cools down to a certain extent. (Temperature where the pipe is cool enough to be touched by hands)

7)Remove the flux completely after brazing.

Fig 2-5-1

Prevention of oxidation during brazing

M

Flow meter

Stop valve

Nitrogen gas cylinder

From nitrogen cylinder

Pipe

Nitrogen gas

Robber plug

14

Page 15
Image 15
Toshiba HWS-1402H-E, HWS-802XWHT6-E, HWS-802H-E, HWS-802XWHM3-E, HWS-1402XWHT6-E Fig Prevention of oxidation during brazing