8-4.

6) Defrosting control

Outdoor unit

This control defrosts the outdoor heat exchanger. The temperature sensor (TE sensor) of the outdoor heat exchanger

control

determines frost formation, and then defrosting is performed in the 4-way valve reverse defrosting method.

1)During a heating operation, defrosting is performed when the TE sensor meets any of the conditions in A through D zones.

2)During defrosting, when TE sensor maintains 12°C or higher for 3 seconds or 7°C TE < 12°C for a minute, the defrosting ends. Also, when defrosting continues for 10 minutes even if the TE sensor temperature is below 7°C, the defrosting ends.

3)After the defrosting, stop the compressor for approx. 40 seconds before starting a heating operation.

4)Switching the jumper "J805" and "J806" of the outdoor control board can change the time of d above mentioned. (Factory setting: 150 minutes)

Heating operation starts

 

 

TE 0

 

10

15

39

45

 

 

55

 

 

d

 

 

 

[min]

 

 

 

 

[°C]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A zone

 

 

 

 

 

 

 

-10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D zone

 

*1 In 10 to 15 minutes after the heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

zone

 

 

 

 

 

 

-23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation starts, the lowest value of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TE is recorded as TEO, and the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(-25)*2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lowest temperature of To as ToO.

 

 

 

 

 

 

 

*1

 

 

 

 

 

C zone

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Inside brackets: For 802H-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To Normal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A Zone

 

 

 

 

 

 

 

Maintain " (TEO - TE) - (ToO - To)

 

3°C" for 20 secs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B Zone

 

 

 

 

 

 

 

Maintain " (TEO - TE) - (ToO - To)

 

2°C" for 20 secs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C Zone

 

 

 

 

 

 

 

Maintain " TE

 

-23°C" for 20 secs (1102, 1402H-E)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maintain " TE < -25°C" for 20 secs (802H-E)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D Zone

 

 

 

 

 

Accumulate compressor operation status of TE < -2°C for 150 mins

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To Normal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A Zone

 

 

 

 

 

 

 

Maintain " TEO - TE

3°C" for 20 secs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B Zone

 

 

 

 

 

 

 

Maintain " TEO - TE

2°C" for 20 secs

 

 

C Zone

 

 

 

 

 

 

 

Maintain " TE

 

-23°C" for 20 secs (1102, 1402H-E)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maintain " TE < -25°C" for 20 secs (802H-E)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D Zone

 

 

 

 

 

Accumulate compressor operation status of TE < -2°C for 150 mins

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Jumper switching

 

 

 

 

 

 

 

 

 

 

 

 

 

O: Short circuit ×: Open

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J805

 

 

 

J806

d (1102,1402H-E)

 

 

 

 

 

 

 

d (802H-E)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O

 

 

 

O

150 mins (Factory setting)

 

 

150 mins (Factory setting)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O

 

 

 

×

 

 

90 mins

 

 

 

 

 

 

 

90 mins

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

×

 

 

 

O

 

 

60 mins

 

 

 

 

 

 

 

60 mins

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

×

 

 

 

×

 

 

30 mins

 

 

 

 

 

 

 

30 mins

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defrosting operation

Compressor

ON

OFF

Outdoor fan

ON

OFF

4-way valve

ON

OFF

 

500pulse

200pulse

Outdoor PMV 0pulse

0s

30s

40s

0s

10s

30s

40s

61

Page 62
Image 62
Toshiba HWS-802XWHM3-E, HWS-802XWHT6-E, HWS-802H-E, HWS-1402H-E Heating operation starts, Inside brackets For 802H-E, Off