Diagnostic functional operation

 

 

Number of

 

Check

 

 

 

Determination and action

abnormalities

Detailed

 

 

 

code

 

Backup

Automat

for

item

Operational cause

 

 

present

ic reset

 

confirmation

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation of case thermostat

 

 

1. Check the refrigeration cycle (gas

 

 

 

When the case thermostat exceeds

 

 

leak).

 

 

 

125°C.

 

 

2. Check the case thermostat and

 

 

H04

 

O

×

connector.

4

92

 

3. Check that the service valve is fully

 

 

 

 

 

 

 

 

 

 

open.

 

 

 

 

 

 

4. Defect of the pulse motor valve.

 

 

 

 

 

 

5. Check for a kinked piping.

 

 

 

 

 

 

 

 

 

L10

Unset service PC board jumper

O

×

1. Cut J800-J803.

1

92

Jumpers J800-J803 have not been cut.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The communication between the

 

 

 

 

 

L29

outdoor PC board MUCs error

O

×

1. Replace the outdoor control board.

1

93

No communication signal between IPDU

 

 

 

 

 

 

 

and CDB.

 

 

 

 

 

 

 

 

 

 

 

 

 

The outlet temperature error

 

 

1. Check the refrigeration cycle (gas

 

 

 

When the discharge temperature sensor

 

 

leak).

 

 

P03

(TD) exceeds 111°C.

O

×

2. Defect of the pulse motor valve.

4

94

 

 

 

 

3. Check the resistance value of the

 

 

 

 

 

 

discharge temperature sensor (TD).

 

 

 

 

 

 

 

 

 

P04

The high pressure switch error

O

×

 

10

94

 

 

 

 

 

 

 

 

The power supply voltage error

 

 

1. Check the power supply voltage.

 

 

P05

When the power supply voltage is

O

×

4

94

(AC230 V±23 V)

 

extremely high or low.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overheating of heat-sink error

 

 

1. Check the thread fastening and

 

 

 

When the heat-sink exceeds 105°C.

 

 

heat-sink grease between the

 

 

 

 

 

 

outdoor control board and the heat-

 

 

P07

 

O

×

sink.

4

95

 

 

 

 

 

 

2. Check the heat-sink fan duct.

 

 

 

 

 

 

3. Check the resistance value of the

 

 

 

 

 

 

heat-sink temperature sensor (TH).

 

 

 

 

 

 

 

 

 

 

Detection of gas leak

 

 

1. Check the refrigeration cycle (gas

 

 

 

When the discharge temperature sensor

 

 

leak).

 

 

 

(TD) exceeds 106°C for consecutive 10

 

 

2. Check that the service valve is fully

 

 

 

min.

 

 

open.

 

 

 

 

 

 

 

 

P15

When the suction temperature sensor

O

×

3. Defect of the pulse motor valve.

4

95

 

 

4. Check for a kinked piping.

 

(TS) exceeds 60°C for cooling or 40°C

 

 

 

 

 

for heating for 10 consecutive min.

 

 

5. Check the resistance value of the

 

 

 

 

 

 

discharge temperature sensor (TD)

 

 

 

 

 

 

and the suction temperature sensor

 

 

 

 

 

 

(TS).

 

 

 

 

 

 

 

 

 

 

The 4-way valve inversion error

 

 

1. Check the operation of the 4-way

 

 

 

When the heat exchange temperature

 

 

valve unit or the coil characteristics.

 

 

 

sensor (TE) exceeds 30°C or the suction

 

 

2. Defect of the pulse motor valve.

 

 

P19

temperature sensor (TS) exceeds 50°C

O

×

3. Check the resistance value of the

4

96

 

 

 

 

 

 

during the heat pump operation.

 

 

heat exchange temperature sensor

 

 

 

 

 

 

 

 

 

 

 

 

(TE) and the suction temperature

 

 

 

 

 

 

sensor (TS).

 

 

 

 

 

 

 

 

 

71