Toshiba HWS-1402XWHT9-E, HWS-802XWHT6-E, HWS-802H-E, HWS-802XWHM3-E, HWS-3001CSHM3-E(-UK) Check code

Models: HWS-1402XWHT9-E HWS-1402XWHM3-E HWS-1402XWHT6-E HWS-1501CSHM3-E(-UK) HWS-1402H-E HWS-2101CSHM3-E(-UK) HWS-3001CSHM3-E(-UK) HWS-802XWHM3-E HWS-802H-E HWS-802XWHT6-E

1 168
Download 168 pages 43.83 Kb
Page 99
Image 99
Manual background

Check code

Outdoor LED

 

Check and Action procedure

 

 

indication

(No specific description indicates outdoor unit parts.)

 

 

 

 

 

 

 

 

 

[P22]

<Indication 1> <Indication 2>

[Blower system failure]

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

Power voltage is normal

 

 

Check wiring

 

 

 

 

 

 

 

 

 

(230ACV ± 23V)

 

 

 

Request power source repair

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

When not energized, the fan motor can be smoothly rotated by hand. Fan motor coil resistance is normal. Between red - white leads 12 -20Manual background Between white - black leads 12 - 20Manual background Between black - red leads 12 - 20Manual background

Yes

Check outdoor control board If defective, replace it

Outdoor fan sole operation check

No

Manual backgroundManual background Replace fan motor

1)With the dip switch SW804 set as in the table below, pressing SW801 for approx. 1 second can check the outdoor fan sole operation. Perform this check to determine which of upper or lower fan has a problem.

When SW801 is pressed again for 1 second or when 2 minutes has passed, the fan stops. 2)After the check, set all the SW804 dip switches to OFF.

Outdoor fan sole operation

SW804 SW801

 

 

 

4

 

 

 

3

 

 

 

2

ON

 

 

 

1

 

 

 

 

Press

[P26]

<Indication 1> <Indication 2>

[Compressor drive element shorted out]

 

 

 

 

The connection between compressor

No

 

 

 

 

lead and reactor is correct.

 

 

 

 

 

 

 

 

 

(Check with wiring

diagram)

 

 

 

 

 

 

 

Yes

 

 

 

 

 

A operation without

compressor lead

No

 

 

 

 

does not cause the same problem.

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor check

 

 

 

 

 

 

 

(rare short circuit, etc.)

 

 

 

 

 

 

 

If defective, replace it

 

 

 

 

 

 

 

 

 

 

 

 

 

[P29]

<Indication 1> <Indication 2>

[Position detection circuit failure]

 

 

 

 

 

 

 

 

 

 

 

 

 

Check outdoor control board

 

 

 

 

 

 

 

 

If defective, replace it

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual backgroundManual background Correct wiring

Manual backgroundManual background Replace outdoor board

98

Page 99
Image 99
Toshiba HWS-1402XWHT9-E, HWS-802XWHT6-E, HWS-802H-E, HWS-802XWHM3-E, HWS-3001CSHM3-E(-UK), HWS-2101CSHM3-E(-UK) Check code