Air vent valve

Pressure relief valve

Expansion vessel

set : 3bar

 

set : 1bar

 

 

Booster heater (local)

Boiler (local)

zone1

Fan coil unit

7-1. Water

7

32

Pressure switch 4.15MPa

Low pressure sensor

TC

Thermal protector Single operation set : 95 ± 5°C

TWO

Backup heater

Ø1 : 3kW

Ø3 : 6kW

Ø3 : 9kW

Water heat exchanger

max : 10bar

Pressure relief

Set value : 7bar(UK)

THO

Thermal protector

(auto)

set : 75 ± 3°CAC pump max : 10bar

Menometer gage : - 6bar

Water vent valve

Flow sw

TWI

Water outlet

Safety valve set : 3.5bar

M

Motorized 3-way valve

(locally procured)

 

 

AC230V

Strainer

(locally procured)

40 mesh

Drain cock for water charge

(locally procured)

Relief valve(UK)

90°C

10 bar

By-pass valve

(locally procured)

2-way valve for

 

cooling mode

 

(locally procured)

Radiator unit

AC230V

 

 

By-pass valve

 

(locally procured)

zone2

Moterized mixing valve

System Diagram

Refrigeration Cycle / Water

Outdoor unit

8,11,14kw

Thermal cut-out (manual reset) 82°C (+3k/-2k)

Reducing valve(UK)

3.5bar

Water inlet

TTW

Cylinder heater

Ø1 : 2.75kW

AC pump

(locally procured)

TFI

Floor heating

(locally procured)

AC230V

M

System

Local hot water system

Hot water cylinder

Buffer tank(locally procured)

Diagram

Page 33
Image 33
Toshiba HWS-3001CSHM3-E(-UK), HWS-802XWHT6-E, HWS-802H-E, HWS-802XWHM3-E, HWS-2101CSHM3-E(-UK) Water, System Diagram