Toshiba HWS-3001CSHM3-E(-UK), HWS-802H-E System Diagram, Refrigeration Cycle / Water

Models: HWS-1402XWHT9-E HWS-1402XWHM3-E HWS-1402XWHT6-E HWS-1501CSHM3-E(-UK) HWS-1402H-E HWS-2101CSHM3-E(-UK) HWS-3001CSHM3-E(-UK) HWS-802XWHM3-E HWS-802H-E HWS-802XWHT6-E

1 168
Download 168 pages 43.83 Kb
Page 33
Image 33
7-1. Water

 

Air vent valve

Pressure relief valve

Expansion vessel

set : 3bar

 

set : 1bar

 

 

Booster heater (local)

Boiler (local)

zone1

Fan coil unit

7-1. Water

7

32

Pressure switch 4.15MPa

Low pressure sensor

TC

Thermal protector Single operation set : 95 ± 5°C

TWO

Backup heater

Ø1 : 3kW

Ø3 : 6kW

Ø3 : 9kW

Water heat exchanger

max : 10bar

Pressure relief

Set value : 7bar(UK)

THO

Thermal protector

(auto)

set : 75 ± 3°CAC pump max : 10bar

Menometer gage : - 6bar

Water vent valve

Flow sw

TWI

Water outlet

Safety valve set : 3.5bar

M

Motorized 3-way valve

(locally procured)

 

 

AC230V

Strainer

(locally procured)

40 mesh

Drain cock for water charge

(locally procured)

Relief valve(UK)

90°C

10 bar

By-pass valve

(locally procured)

2-way valve for

 

cooling mode

 

(locally procured)

Radiator unit

AC230V

 

 

By-pass valve

 

(locally procured)

zone2

Moterized mixing valve

System Diagram

Refrigeration Cycle / Water

Outdoor unit

8,11,14kw

Thermal cut-out (manual reset) 82°C (+3k/-2k)

Reducing valve(UK)

3.5bar

Water inlet

TTW

Cylinder heater

Ø1 : 2.75kW

AC pump

(locally procured)

TFI

Floor heating

(locally procured)

AC230V

System DiagramM

System

Local hot water system

Hot water cylinder

Buffer tank(locally procured)

Diagram

Page 33
Image 33
Toshiba HWS-3001CSHM3-E(-UK), HWS-802XWHT6-E, HWS-802H-E System Diagram, Refrigeration Cycle / Water