Operation | SDC / DHC |
|
|
Setting time for automatic return
Setting range
Factory setting
If the ¤ button is pressed and held for approx. 3 s, the INFO TIME parameter appears.
With this parameter, the time it takes for automatic return to the basic display can be specified.
OFF | No return. The last selected information display |
| continuously remains in the basic display until the |
| next change. |
1 ... 10 min | Automatic return from the information level after the |
| specified time (in 0.5 minute increments). |
OFF |
|
4.1.2.8"Manual mode" / "Emission measurement" button
4.1.2.8.1Manual mode
C C
If this button is pressed and held longer than 5 s in the basic display, the controller is switched to manual mode. In this operating mode, the required heat generator temperature is specified manually with the input button î according to the respective heating need.
A controller set to manual mode has no effect in heat circuit expansion.
The heat generator setpoint is set between the minimum and maximum heat generator temperatures and appears flashing at the bottom
Application Controller malfunctions (emergency operation), errors
NOTE The maximum heat generator temperature limit is paramount to the heat generator switching differential and stops the heat generator in case of exceedance.
With control devices operated purely as a heating circuit expansion, the setting of the temperature has no effect.
28 |