Honeywell SDC manual Undoing deactivation, Factory setting 20 C, Parameter reset

Models: SDC

1 64
Download 64 pages 29.07 Kb
Page 55
Image 55

SDC / DHC

Operation

 

 

Undoing deactivation

Deactivation is undone when the averaged and current outside temperature exceeds the set value by 1 K.

The summer deactivation function is undone:

In case of an outside sensor defect

In case frost protection is active

NOTE During deactivation phases (standby mode, manual summer operation, summer deactivation) lasting longer than 24 hours all pumps are switched on for approx. 20 s and the mixers are temporarily opened during this time to protect against blocking by corrosion.

In connection with a second outside sensor, the current averaged outside temperature is accepted for summer deactivation if the average value of both sensors is specified during outside sensor assignment.

Active summer deactivation is represented by a beach umbrella symbol in the basic display.

Only active in the AUTOMATIC operating mode.

Factory setting 20 °C

Setting range OFF, set value of system frost protection to 40 °C

4.2.3.5Parameter reset

With the reset parameter, it is possible to reset any inadvertently made changes in the parameter menu to the factory setting.

ATTENTION

A reset should only be carried out if all individually entered values are to be replaced by the values specified at the factory.

Setting ► When the PARAM. RESETdisplay flashes, press the input button î.

SET flashes in the display.

Press and hold the input button î for 5 s.

EN2H-0220GE51 R0308

55