SDC / DHC | Operation |
|
|
NOTE If a
4.2.5"Direct Heating Circuit" / "Mixed Heating Circuit 1" / "Mixed Heating Circuit 2" menu
These menus contain all parameters required to program the heating circuit, except the switch time programs. Max. one direct heating circuit and two mixed heating circuits (mixed heating circuit 1 and mixed heating circuit 2) are available as heating circuits.
The following described heating circuit parameters are available separately for setting for each heating circuit.
4.2.5.1Reduced operation
During reduced operation, you can select between two operating modes.
Factory setting | ECO |
Setting range | ECO, RED |
Set values | RED (lowering operation) |
| The heating circuit pump of the direct heating circuit continues |
| functioning during reduced operation (see 4.2.3.2 Time program, |
| pg. 52). The flow temperature is determined based on the lowered |
| room temperature from the associated reduced heating curve. |
| The set maximum temperature is not undershot. |
Application | Building with minimal insulation values and high cooling loss. |
| 57 |