Honeywell SDC manual Cancellation

Models: SDC

1 64
Download 64 pages 29.07 Kb
Page 29
Image 29

SDC / DHC

 

 

Operation

 

 

 

The last value to which the control device adjusted the heat

 

generator temperature appears as a recommendation.

Cancellation

Press

button or

button, to return to the last selected

 

operating mode.

 

4.1.2.8.2Emission measurement (not with district heating controllers)

Function

Application

Cancellation

ATTENTION

Emission measurements may only be carried out by the chimney sweep.

Pressing the button controls the heat generator for a duration of 20 min based on the set maximum temperature limit. The remaining time is displayed and counted down.

With two-stage heat generators, both stages are in operation (measurement at nominal output).

The heat generator is adjusted to the maximum heat generator temperature. All heating circuits and the hot-water production adjust their setpoint to the respective maximum temperature.

ATTENTION

There is a danger of scalding by hot water, as the hot-water temperature can exceed the set setpoint temperature.

Emission measurement by the chimney sweep.

Emission measurement can be cancelled at any time with the

or button.

EN2H-0220GE51 R0308

29

Page 29
Image 29
Honeywell SDC manual Cancellation