If a reset is carried out, the RESET OK confirmation appears briefly. Verification is then started with a call-up of the first parameter in the respective menu once again.

After the parameter values are reset, a return to the first parameter in the "System Parameter" menu occurs.

4.2.4"DHW" menu

This menu contains all parameters required to program the hot- water circuit, except the hot-water switching time programs.

4.2.4.1Night-time hot-water temperature

This parameter specifies the temperature in the hot-water generator between the operational-readiness times in automatic mode.

Factory setting 40 °C

Setting range 5 °C to set normal hot-water temperature value

NOTE If a hot-water thermostat (see parameter 05 = transducer for hot- water circuit) is used to detect the hot-water temperature, this parameter is skipped.

4.2.4.2Legionella protection day Factory setting OFF

Setting range

Set values

OFF, MO to SU, ALL

OFF

The legionella protection function is not active.

MO to SU

Legionella protection is activated on the selected

 

day of the week at the legionella protection time set

 

in the following parameter.

ALL

The legionella protection function is activated daily

 

at the legionella protection time set in the next

 

parameter.