Operation

SDC / DHC

 

 

4.2.3.3.3

Setting

C

4.2.3.4

Individualised operating mode for each heating circuit

Each heating circuit can be assigned an individualised operating mode.

Press button.

Select desired heating circuit (HC, MC-1 or MC-2) by turning the input button î.

Confirm selected circuit by pressing the input button î.

Select flashing operating mode by turning the input button î.

Confirm set operating mode by pressing the button or the input button î.

With short-term operating modes (ABSENT, PARTY), set desired target value by turning the input button î and confirm set value by pressing the input button î.

Alternative: Automatic acceptance of the value after the set information time (see 4.1.2.7 "System information" button, pg. 26).

Summer / Heating limit

This parameter specifies the end of heating operation depending on the outside temperature based on the following criteria:

Quick increase in outside temperature

If the averaged outside temperature is below the set value and the current outside temperature is 2 K above the set value, heating operation is interrupted.

Slow increase in outside temperature

Deactivation is also initiated when the averaged and current outside temperature exceeds the set value.

54