Operation | SDC / DHC |
|
|
4.2.3.3.3
Setting
C |
4.2.3.4
Individualised operating mode for each heating circuit
Each heating circuit can be assigned an individualised operating mode.
►Press button.
►Select desired heating circuit (HC,
►Confirm selected circuit by pressing the input button î.
►Select flashing operating mode by turning the input button î.
►Confirm set operating mode by pressing the button or the input button î.
►With
Alternative: Automatic acceptance of the value after the set information time (see 4.1.2.7 "System information" button, pg. 26).
Summer / Heating limit
This parameter specifies the end of heating operation depending on the outside temperature based on the following criteria:
Quick increase in outside temperature
If the averaged outside temperature is below the set value and the current outside temperature is 2 K above the set value, heating operation is interrupted.
Slow increase in outside temperature
Deactivation is also initiated when the averaged and current outside temperature exceeds the set value.
54 |