b) KML-631MWH

b) KML-631MWH

(1) Connection to an Open Drain System

Condenser Water

Minimum Condenser

Condenser Drain

Minimum Condenser

Supply Inlet

Water Supply Line Size

Outlet

Drain Line Size

 

 

 

 

1/2" Female Pipe

1/4" Nominal ID Copper

3/8" Female Pipe

1/4" Nominal ID Hard Pipe

Thread (FPT)

Water Tubing or Equivalent

Thread (FPT)

or Equivalent

 

 

 

 

A condenser water supply line shut-off valve and drain valve must be installed.

In some areas, a back flow preventer may be required in the cooling water circuit.

In order to maintain the proper high side pressure, the condenser water supply inlet temperature should not drop below 45°F (7°C) and the condenser drain outlet temperature must be in the 104°F to 115°F (40°C to 46°C) range. Once the icemaker installation

is complete, confirm the condenser drain outlet temperature 5 minutes after a freeze cycle starts. If the condenser drain outlet temperature is not in the proper range, use a flat blade screwdriver to rotate the adjustment screw on the waterregulating valve until the temperature is in the proper range (rotate counterclockwise to raise temperature or clockwise to lower temperature).

 

 

Minimum 1/4" Nominal ID Copper

Icemaker Water

 

Water Tubing or Equivalent

 

 

 

Supply Inlet

 

Icemaker

 

1/2" FPT

 

 

Shut-Off Valve

 

 

 

Condenser

 

 

 

Drain Outlet

 

 

 

3/8" FPT

 

 

 

Condenser Water

 

 

Drain Valve

Supply Inlet

 

 

 

1/2" FPT

 

 

 

Vent Tube

 

 

 

Icemaker

Ice

 

 

Storage

 

Be sure there is sufficient

Drain Outlet

 

Bin

 

extra water supply line and

3/4" FPT

 

 

 

drain line for the appliance

 

 

 

Minimum 1/4"

 

 

to be pulled out for service.

 

 

 

Nominal ID

 

 

Separate piping to approved

Hard Pipe or

 

 

drain. Leave a 2-inch (5-cm)

Equivalent

 

 

vertical air gap between the

 

 

 

end of each pipe and the

Bin Drain Outlet

 

 

drain.

3/4" FPT

 

 

 

 

 

Vent Tube

2-inch (5-cm) air gap

 

 

 

 

 

Minimum 3/4" Nominal ID

 

 

 

Hard Pipe or Equivalent

 

Fig. 7

Water-Cooled Models

Floor Drain

Model Shown:

 

Connection to an Open Drain System

KML-631MWH

22