Hoshizaki MWH KML-351MAH, MWH KML-451MAH Water-CooledModels, Connection to a Closed Loop System

Models: MWH KML-351MAH KML-250MAH MWH KML-631MAH MWH MRH MWH KML-451MAH

1 40
Download 40 pages 33.48 Kb
Page 23
Image 23
Manual background

(2) Connection to a Closed Loop System

Condenser Water

Minimum Condenser

Condenser

Minimum Condenser

Supply Inlet

Water Supply Line Size

Return Outlet

Return Line Size

 

 

 

 

1/2" Female Pipe

1/4" Nominal ID Copper

3/8" Female Pipe

1/4" Nominal ID Copper

Thread (FPT)

Water Tubing or Equivalent

Thread (FPT)

Water Tubing or Equivalent

 

 

 

 

Shut-off valves and drain valves must be installed at both the condenser water supply inlet and condenser return outlet.

Minimum water flow to the condenser is 4 GPM.

The pressure differential between the condenser water supply inlet and condenser return outlet must be no less than 10 PSIG.

When using a glycol blend, the solution mixture should be less than 30% glycol.

In order to maintain the proper high side pressure, the condenser water supply inlet temperature should not drop below 45°F (7°C) and the condenser return outlet temperature must be in the 104°F to 115°F (40°C to 46°C) range. Once the icemaker installation is complete, confirm the condenser return outlet temperature 5 minutes after a freeze cycle starts. If the condenser return outlet temperature is not in the proper range, use a flat blade screwdriver to rotate the adjustment screw on the waterregulating valve until the temperature is in the proper range (rotate counterclockwise to raise temperature or clockwise to lower temperature).

Icemaker Water

Supply Inlet

1/2" FPT

Condenser

Return Outlet

3/8" FPT

Condenser Water

Supply Inlet

1/2" FPT

Vent Tube

Icemaker

Drain Outlet

3/4" FPT

Bin Drain Outlet

3/4" FPT

Fig. 8

Model Shown: KML-631MWH

Minimum 1/4" Nominal ID Copper

Water Tubing or Equivalent

Icemaker

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background Shut-Off Valve

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background Drain Valve

Ice

Be sure there is sufficient

Storage

extra water supply line and

Bin

drain line for the appliance

 

to be pulled out for service.

Separate piping to approved drain. Leave a 2-inch (5-cm) vertical air gap between the end of each pipe and the drain.

Vent Tube

 

2-inch (5-cm) air gap

Minimum 3/4" Nominal ID

 

 

 

 

 

 

 

 

 

 

 

 

Hard Pipe or Equivalent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Water-Cooled Models

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connection to a Closed Loop System

 

Floor Drain

 

 

 

23

Page 23
Image 23
Hoshizaki MWH KML-351MAH, MWH KML-451MAH, MRH, MWH KML-631MAH Water-CooledModels, Connection to a Closed Loop System