Control cabinet component identification

All circuits in the control cabinet are labeled with the panel name and circuit breaker number.

Each IT section has one control cabinet that houses the various control components for that IT section. IT section A control cabinet

The ECS and fire panel controls are located in the IT section A control cabinet.

Item

Component

Description

 

 

 

1

VESDA air sampling smoke

An early warning laser scan smoke detection unit

 

detection unit

 

2

Fire alarm control panel

Controls all fire systems within the HP POD 240e NA,

 

 

including the smoke detection system and manual fire pulls

 

 

Includes a battery backup system to provide backup power to

 

 

the fire system in the event of power loss to the HP POD 240e

 

 

NA

 

 

 

3

UPS

Provides backup power to the IT section A VESDA in the event of

 

 

power loss to the HP POD 240e NA

4

Access control module

Controls and organizes information that is monitored by the HP

 

 

POD 240e NA access control components

5

Customer access control

Provides a location for the facility access control components and

 

junction box

connects the facility to the HP POD 240e NA

 

 

 

6

ECS relays

Relays for the ECS control

7

ECS modules and terminal

Used for ECS communication, I/O connections, and terminal block

 

blocks

connections

8

House power fuses and terminal

Provide house power to the HP POD 240e NA convenience outlets

 

blocks

and lighting

 

 

 

9

Power supply*

Provides 24V DC power to the PLC, ECS, and LED lighting

10

UPS*

Provides battery backup power to the PLC and ECS in the event of

 

 

power loss to the HP POD 240e NA

11

240/120V transformer

Provides house power to IT section A convenience outlets

Component identification 16