The Top screen displays the following information for each IT section.

Information displayed

Description

 

 

CA pressure

Indicates the minimum, maximum, and average

 

pressure values for each IT section

CA RH

Indicates the minimum, maximum, and average

 

relative humidity percentages from each IT section

CA combo temperature

Indicates the minimum, maximum, and average

 

temperature values for each IT section

 

 

Return temperature

Indicates the minimum, maximum, and average

 

return temperature values for each IT section

 

 

HA pressure

Indicates the minimum, maximum, and average

 

pressure values for the hot aisle

Hot aisle temperature

Indicates the hot aisle temperature at three different

 

locations in the hot aisle.

Min and Max value sensor

Indicates the specific sensor that is reading the

number

minimum and maximum value for each statistic

Fan speed

Indicates the exhaust fan speed percentage

Environmental control system 44

Page 44
Image 44
HP Performance Optimized Data Center (POD) 240a manual Ca Rh