The AD detail screen displays the following minimum and maximum alarm setpoint ranges that you can configure:

Setpoint displayed

Description

 

 

HA return temperature

Indicates the temperature reading from the hot

 

aisle

 

 

HA static pressure

Indicates the pressure value reading from the hot

 

aisle in relation to the external ambient

 

temperature

 

 

CA wall temperature

Indicates the temperature from the wall sensor

 

located in the IT sections

 

 

CA temperature combo

Indicates the average temperature from the wall

 

sensor and discharge temperature sensor

CA relative humidity

Indicates the relative humidity percentage from the

 

wall sensor

CA dew point

Indicates the dew point temperature from the wall

 

sensor

 

 

CA static pressure

Indicates the pressure value reading from the IT

 

sections in relation to the external ambient

 

pressure

 

 

CA discharge temperature

Indicates the discharge air temperature

The AD detail screen displays the following operational parameters for each AHU:

Environmental control system 46