WARNING: To avoid the risk of personal injury or loss of life, all personnel must comply with electrical warning labels when operating and maintaining the electrical panels and systems of the HP POD 240e NA.

For the external electrical power component locations, see "Electrical power component identification (on page 13)."

Power distribution: electrical busway system

Each IT section of the HP POD 240e NA is protected by an electrical circuit breaker panel located on the end of the HP POD 240e NA.

End view shown

The following specifications are for each IT section electrical circuit breaker panel.

Feature

Specification

 

 

Number of busways

8

Frequency

60 Hz

Amps (per busway)

200A

Voltage (per busway)

415V, wye

Grounding

Copper

Busway conductors

3-phase + neutral + equipment ground

Power distribution: Adiabatic system

The Adiabatic units are powered and protected by an electrical circuit breaker panel located on the end of the HP POD 240e NA. Within each AHU electrical cabinet, there are two panels that provide power to the Adiabatic units.