Information displayed

Description

 

 

AD detail

Indicates detailed information for each Adiabatic

 

unit:

 

Hot aisle air

 

Return damper

 

Isolation damper

 

Water usage

 

Fan speed

 

Cold aisle air

 

Bypass damper

 

Outdoor damper

 

Outdoor air

 

 

ECS cabinet

Indicates the status of the ECS system and displays

 

the following alarm indicators:

 

EPO

 

Breaker

 

Power source

 

UPS

 

Door open

 

VESDA

 

 

 

The ECS component icon colors indicate the component status:

Green—No alarm conditions exist and the component is operating within normal parameters.

Amber—A warning alarm condition or notification for that component exists.

Red—A critical alarm condition for that component exists.

Gray—A loss of communication for that component exists or an AHU is powered off.

For more information about alarm conditions, see "Alarms screen (on page 51)."

To navigate to another screen, select one of the menu options on the navigation toolbar at the top of the screen. For more information, see "Navigating the ECS interface (on page 42)."

AD detail screen

The AD detail screen displays detailed information for the Adiabatic unit selected. The Adiabatic unit number appears at the top of the screen.

IMPORTANT: The ECS parameters must only be set by qualified service personnel.

Environmental control system 45