Electrical power component identification

WARNING: To avoid the risk of personal injury or loss of life, all personnel must comply with PPE requirements when opening or working inside areas of the HP POD 240e NA that are marked as hazardous voltage, per NFPA 70E in accordance with NEC (NA) and IEC (EMEA and APJ).

WARNING: To avoid the risk of personal injury or loss of life, all personnel must comply with electrical warning labels when operating and maintaining the electrical panels and systems of the HP POD 240e NA.

End view shown

Item

Component

Description

 

 

 

1

Demarcation box

Customer communication connection point:

 

 

ECS

 

 

Access control

 

 

Phone

 

 

 

2

Fire box

Connection location for fire emergency and VESDAnet signals

3

415/240V 3-phase, wye,

A feed power for IT Section A electrical busways and house power

 

4-wire

 

 

4

415/240V 3-phase, wye,

B feed power for IT Section A electrical busways and house power

 

4-wire

 

 

5

Mechanical power feed

A and B feed power for the IT Section A AHU

 

cabinet

 

 

6

Mechanical power feed

A and B feed power for the IT Section B AHU

 

cabinet

 

 

7

415/240V 3-phase, wye,

B feed power for IT Section B electrical busways and house power

 

4-wire

 

 

8

415/240V 3-phase, wye,

A feed power for IT Section B electrical busways and house power

 

4-wire

 

 

Main breaker locations

Component identification 13