Callout

Sensor

Quantity per

Description

 

 

hot aisle

 

 

 

 

 

1

Temperature sensors

3

Monitor the temperature in various locations

 

 

 

throughout the hot aisle of the HP POD 240e

 

 

 

NA

 

 

 

Report data to the ECS

 

 

 

 

2

Hot aisle pressure sensor

12

Monitor and report hot aisle pressure

 

probes

 

Report data to the AHU controllers

 

 

 

 

3

Hot aisle temperature sensor

12

Monitor and report hot aisle temperature

 

probes

 

Report data to the AHU controllers

 

 

 

 

Outdoor air sensors

There is one sensor mounted on each Adiabatic unit that monitors the temperature and humidity of the outdoor air. Each sensor reports the data to the AHU controller.

Adiabatic units

Each IT section of the HP POD 240e NA has six Adiabatic units that maintain the differential pressure and temperature parameters within the HP POD 240e NA.

For more information about the required power for the Adiabatic units, see "Power distribution: Adiabatic system (on page 28)."

Controlling the hot aisle fans

There are 10 exhaust fans located in the hot aisle of the HP POD 240e NA.

Side view shown

The HP POD 240e NA fans operate at variable speeds (0-100%) to maintain predetermined parameters programmed into the AHU. For more information about the fan mode, see "AHU theory of operation (on page 62)".

Environmental control system 60

Page 60
Image 60