Information displayed

Description

 

 

Static pressure

Indicates the cold and hot aisle static pressure

 

readings for each Adiabatic in relation to the

 

external ambient pressure

 

 

Temps

Indicates the cold and hot aisle temperature

 

readings for each Adiabatic unit

 

 

Fan speed

Indicates the fan speed for each Adiabatic unit

Water valve

Indicates the water valve percentage for each

 

Adiabatic unit

Dampers

Indicates the damper position for each Adiabatic

 

unit

 

 

To change the charts that display at the bottom of the screen:

1.Click a chart to bring up the chart menu.

2.Select the information that you want to view.

Alarms chart

The alarms chart displays critical and warning alarms that are active in the system. For more information, see "Alarms screen (on page 51)."

Electrical Cabinets screen

The Electrical Cabinets screen displays detailed power meter information that is monitored from the HP POD 240e NA power input. This screen displays the voltage and current average for all 3-phase electrical feeds. The apparent and real power values are the sum of all 3-phase electrical feeds. The values shown on this screen are included in the PUE calculations for the HP POD 240e NA.

The power information that displays on this screen is read-only and cannot be altered.

Static IP addresses can be viewed from this screen when the customer-level password is entered.

IMPORTANT: The ECS system subtracts the power measurements for the house panel from the Starline power measurements to be sure that the PUE measurements are accurate.

Environmental control system 49

Page 49
Image 49
HP Performance Optimized Data Center (POD) 240a manual Electrical Cabinets screen, Alarms chart