2.6.5Event Log
The event log displays up to 1000 controller faults and notices, starting with the most recent event. Events are numbered
Procedure to View Event History
1.Press Select to enter the main menu.
2.Press the down arrow to step down to the event log.
3.Press Select to display the most recent event.
4.Press the down arrow to step to the next event.
5.Use the up and down arrow buttons to view events.
6.Press the Select button to exit the event log.
To stop viewing the event history before the last event, press the select button to return to the main menu.
| Date MO/DA/YEAR |
Event Log | time HR:MN |
| event number, W/S/I, engine hours |
| event name |
Press UP and Down arrow buttons to scroll through events
Date MO/DA/YEAR time HR:MN
event number, W/S/I, engine hours event name
Press Select button at any time to |
|
return to the main menu. |
|
Event codes: |
|
W = Warning |
|
S = Shutdown |
|
I = Informational Notice | tp6810 |
| |
Figure |
|
2.7Model RXT Transfer Switch Operation
The RDC2 generator set/transfer switch controller manages automatic transfer switch (ATS) functions when connected to a Kohlerr Model RXT transfer switch through the ATS interface board. Refer to the Model RXT Operation/Installation Manual for information about the transfer switch operation.
2.7.1Source Availability
The Model RXT transfer switch supplies voltage sensing data to the RDC2 controller through the ATS interface board. If the source voltage falls below the undervoltage dropout setting, the source is considered to have failed. See Figure
Item | Setting |
|
|
Accuracy | ±5% |
Undervoltage Dropout | 90% of Pickup |
|
|
Undervoltage Pickup | 90% of Nominal |
Figure
The RDC2 controller also has a set of power system LEDs below the pushbuttons. The power system LEDs indicate which power sources are available and which source is supplying power to the building. See Figure
Note: The power system LEDs operate only if a Model RXT transfer switch is connected. They will not operate if a Model RDT or RSB transfer switch is used.