Section 5 Troubleshooting
5.1 Introduction
Use the troubleshooting charts in this section to diagnose and correct common problems. First check for simple causes such as a dead engine starting battery, loose connections, or an open circuit breaker. The charts include a list of common problems, possible causes of the problem, and recommended corrective actions.
If the procedures in this manual do not explain how to correct the problem, contact an authorized Kohler distributor/dealer. Maintain a record of repairs and adjustments performed on the equipment. Use the record to help describe the problem and repairs or adjustments made to equipment.
5.2 USB Port
A USB port is located on the front of the controller. Use a USB cable with a
Some controller settings can be adjusted using a laptop computer with Kohlerr SiteTecht software. SiteTech software is available to Kohler authorized distributors and dealers. See
5.3 Fault Messages
The RDC2 controller displays fault messages to aid in troubleshooting. Fault messages, descriptions, and recommended checks are listed in Figure
Identify and correct the cause of the fault condition. Then reset the controller after a fault shutdown. See Section 2.6.4.
5.4 Circuit Protection
If the generator set circuit breaker trips or the fuses blow repeatedly, contact an authorized Kohler distributor/ dealer for service.
5.4.1Load Circuit Breaker
The load circuit breaker interrupts the generator output in the event of a fault in the wiring between the generator and the load. If the circuit breaker trips, reduce the load and switch the breaker back to the ON position. Refer to the service views in Section 1 for the location of the circuit breaker.
5.4.2Fuses
Always identify and correct the cause of a blown fuse before restarting the generator set. Refer to Figure
Fan Fuses. Three 30 amp fan fuses are located in the fan fuse and relay box. See Section 1, Service Views, for location.
5.4.3Controller Internal Circuit Protection
The controller is equipped with internal circuit protection. Press OFF to reset.
Section 5 Troubleshooting 61 |