Kohler 24RCL manual Frequency High

Models: 24RCL

1 68
Download 68 pages 26.64 Kb
Page 25
Image 25

Fault (RDC2)

Fault (OnCuer

Condition

Check

 

Plus)

 

 

 

 

 

 

Frequency High

High Frequency

Governed frequency exceeds 110% of the

Contact an authorized

Shutdwn

 

system’s frequency setpoint for more than 10

distributor/dealer for service.

 

 

seconds. Function becomes active 10

 

 

 

seconds after engine start (10 second inhibit).

 

 

 

 

 

Frequency Low

Low Frequency

Governed frequency falls below 90% of the

Reduce the load by turning off

Shutdwn

 

system frequency setting for more than

appliances and restart the generator

 

 

10 seconds, or 1 Hz below the system

set.

 

 

frequency setting for more than 60 seconds.

Contact an authorized

 

 

 

 

 

Function becomes active 10 seconds after

distributor/dealer for service.

 

 

engine start (10 second inhibit).

 

 

 

 

 

Genset S/N

Unavailable

Generator set serial number is unavailable.

Contact an authorized

Unaval Warning

Genset Serial

 

distributor/dealer for service. See

 

Number

 

section 3.11.

 

 

 

 

IAT High 1

Iat Higher

Engine manifold air temperature is too high.

Contact an authorized

Warning

Than

 

distributor/dealer for service and

 

Expected 1

 

provide the fault code.

 

 

 

 

IAT Volt Hi

Iat High

The ECM reported an Engine Air

Contact an authorized

Warning

Voltage

Temperature/Manifold Absolute Pressure

distributor/dealer for service and

 

 

Sensor (TMAP) error.

provide the fault code.

 

 

 

 

IAT Volt Lo

Iat Low

The ECM reported an Engine Air

Contact an authorized

Warning

Voltage

Temperature/Manifold Absolute Pressure

distributor/dealer for service and

 

 

Sensor (TMAP) error.

provide the fault code.

 

 

 

 

Invalid Csum

Flash Csum

An ECM error occurred.

Contact an authorized

Warning

Invalid

 

distributor/dealer for service and

 

 

 

provide the fault code.

 

 

 

 

Lo Crank Vlt

Low Cranking

Low cranking voltage. Battery voltage falls

Charge or replace the battery.

Warning

Voltage

below 60% of system battery voltage for more

 

 

 

than 6 seconds while the starter is engaged.

 

 

 

 

 

Locked Rotor

Locked Rotor

No engine rotation is sensed during cranking.

Check the battery.

Shutdwn

 

Shuts down 3 seconds after the fault is

Check for loose connections.

 

 

detected.

 

 

Check for obstruction of alternator or

 

 

 

 

 

 

engine.

 

 

 

Contact an authorized

 

 

 

distributor/dealer for service.

MainPwrOverL

Main Power

Main power overload. An over current fault on

Check for shorted run relay. Check

Shutdwn

Overload

the 70 controller power output (short circuit).

wiring for short circuits.

 

 

 

Contact an authorized

 

 

 

distributor/dealer for service.

Maint Req’d

Maintenance

Engine maintenance is due.

Check the maintenance schedule in

Warning

Required

 

the operation manual for tasks such

 

Warning

 

as changing the oil, spark plugs or the

 

 

 

air filter.

 

 

 

 

Not in Auto

Not In Auto

The generator set is not in Automatic

Press AUTO to place the generator

Warning

 

(standby) mode. Remote start and stop

set in Automatic mode, when

 

 

commands from a transfer switch or remote

appropriate.

 

 

switch will be ignored.

 

 

 

 

 

Oil Pres Low

Low Oil

The engine ECM indicates low oil pressure.

Check for leaks in the lubrication

Shutdwn

Pressure

Note: The low oil pressure shutdown does not

system.

 

 

protect against low oil level. Check the engine

Check the oil level and add oil if the

 

 

oil level regularly as recommended in

level is low.

 

 

Section 4.

Check the oil pressure switch and

 

 

 

 

 

 

wiring.

TP-6905 6/14

Section 2 Generator Set Operation 25

Page 25