Installation
Figure 5 Piping connections for split system fan coil units
UPFLOW (BU) MODELS
HumidifierWater SupplyLine
1/4" OD CU
Suction Refrigerant Line
#11 Quick Connect on Models BU036E/BU035E 1 1/8" OD CU on Models BU060E/BU059E
Condensate Pump Line
1/2" OD CU
Used only if optional condensate pump is ordered.
Condensate Drain
3/4" FPT
Field pitch a min. of 1/8" (3.2mm) per ft. (305mm). Units without a condensate pump have a
Piping outlet locations through the plenum are the same as the unit. See below for descriptions and connection sizes.
Hot Water Return
5/8" OD CU (optional)
Liquid RefrigerantLine
#6 Quick Connect on Models BU036E/BU035E 1/2" OD CU on Models BU060E/BU059E
Hot Water Supply
5/8" OD CU (optional)
Monitoring Panel
PIPINGOUTLET LOCATIONS
(See Cabinet and Floor Planning
Dimensional Data for Piping
Opening Sizes.)