Liebert 3000 installation manual 8.1Calculating Subcooling, Example

Models: 3000

1 76
Download 76 pages 48.63 Kb
Page 72
Image 72
8.1Calculating Subcooling

R407C Refrigerant

Table 34 R407C pressure/temperature chart for subcooling only (liquid measurements)

Temperature

Pressure Gauge

Temperature

Pressure Gauge

Temperature

Pressure Gauge

 

 

 

 

 

 

 

 

 

 

 

 

°F

°C

Psig

kPa

°F

°C

Psig

kPa

°F

°C

Psig

kPa

 

 

 

 

 

 

 

 

 

 

 

 

36.0

2.2

73

500

59.0

15.0

114

786

94.0

34.4

203

1402

 

 

 

 

 

 

 

 

 

 

 

 

37.0

2.8

74

511

60.0

15.6

116

801

96.0

35.6

209

1444

 

 

 

 

 

 

 

 

 

 

 

 

38.0

3.3

76

522

61.0

16.1

118

815

98.0

36.7

216

1488

 

 

 

 

 

 

 

 

 

 

 

 

39.0

3.9

77

533

62.0

16.7

120

830

100.0

37.8

222

1532

 

 

 

 

 

 

 

 

 

 

 

 

40.0

4.4

79

544

63.0

17.2

123

845

102.0

38.9

229

1578

 

 

 

 

 

 

 

 

 

 

 

 

41.0

5.0

81

556

64.0

17.8

125

860

104.0

40.0

236

1624

 

 

 

 

 

 

 

 

 

 

 

 

42.0

5.6

82

567

65.0

18.3

127

875

106.0

41.1

242

1671

 

 

 

 

 

 

 

 

 

 

 

 

43.0

6.1

84

579

66.0

18.9

129

891

108.0

42.2

249

1720

 

 

 

 

 

 

 

 

 

 

 

 

44.0

6.7

86

591

67.0

19.4

131

906

110.0

43.3

257

1769

 

 

 

 

 

 

 

 

 

 

 

 

45.0

7.2

87

602

68.0

20.0

134

922

112.0

44.4

264

1819

 

 

 

 

 

 

 

 

 

 

 

 

46.0

7.8

89

615

69.0

20.6

136

938

114.0

45.6

271

1870

 

 

 

 

 

 

 

 

 

 

 

 

47.0

8.3

91

627

70.0

21.1

138

954

116.0

46.7

279

1922

 

 

 

 

 

 

 

 

 

 

 

 

48.0

8.9

93

639

72.0

22.2

143

987

118.0

47.8

287

1975

 

 

 

 

 

 

 

 

 

 

 

 

49.0

9.4

95

652

74.0

23.3

148

1021

120.0

48.9

294

2029

 

 

 

 

 

 

 

 

 

 

 

 

50.0

10.0

96

664

76.0

24.4

153

1055

122.0

50.0

302

2085

 

 

 

 

 

 

 

 

 

 

 

 

51.0

10.6

98

677

78.0

25.6

158

1090

124.0

51.1

310

2141

 

 

 

 

 

 

 

 

 

 

 

 

52.0

11.1

100

690

80.0

26.7

163

1126

126.0

52.2

319

2198

 

 

 

 

 

 

 

 

 

 

 

 

53.0

11.7

102

704

82.0

27.8

169

1163

128.0

53.3

327

2256

 

 

 

 

 

 

 

 

 

 

 

 

54.0

12.2

104

717

84.0

28.9

174

1201

130.0

54.4

336

2315

 

 

 

 

 

 

 

 

 

 

 

 

55.0

12.8

106

730

86.0

30.0

180

1239

132.0

55.6

345

2376

 

 

 

 

 

 

 

 

 

 

 

 

56.0

13.3

108

744

88.0

31.1

185

1279

134.0

56.7

354

2437

 

 

 

 

 

 

 

 

 

 

 

 

57.0

13.9

110

758

90.0

32.2

191

1319

136.0

57.8

363

2500

 

 

 

 

 

 

 

 

 

 

 

 

58.0

14.4

112

772

92.0

33.3

197

1360

138.0

58.9

372

2563

 

 

 

 

 

 

 

 

 

 

 

 

-

-

-

-

-

-

-

-

140.0

60.0

381

2628

 

 

 

 

 

 

 

 

 

 

 

 

NOTE

Use this table for subcooling calculation ONLY. See Table 33 for superheat or control adjustment.

8.1Calculating Subcooling

Example

Measure the liquid pressure (e.g., 200 psig). Find the liquid saturation temperature at that pressure on Table 34 (e.g., 93°F). Measure the temperature of the liquid line (e.g., 90°F). Subtract the actual temperature from the liquid saturation temperature to obtain the subcooling (e.g., 93 – 90 = 3°F). If the actual temperature is greater than the liquid saturation temperature, then there is no subcooling, and the fluid may be a mixture of liquid and vapor.

Why There Are Two R407C Temperature and Pressure Tables

R407C is a blend of refrigerants that exhibits a temperature “glide” of approximately 8 to 12°F (4 to 7°C. This “glide” is the difference between the liquid and vapor saturation temperatures at a given pressure. Use the correct table for the saturation temperature you need. Table 33 is for super- heat or operating controls. Table 34 is for subcooling only.

66

Page 72