Liebert 3000 installation manual Piping outlet locations through

Models: 3000

1 76
Download 76 pages 48.63 Kb
Page 16
Image 16
Piping outlet locations through

Installation

Figure 7 Piping connections for chilled water self-contained units

UPFLOW (BU) MODELS

Piping outlet locations through

the plenum are the same as the unit. See below for descriptions and connectoin sizes

Humidifier Water Supply

Line 1/4" OD CU

Condenser Re turn Line 7/8" OD CU on Models

BU046WG/BU045WG 1 1/8" OD CU on Models

BU071WG/BU070WG

Condensate Pump Line 1/2" OD CU

Used only if optional condensate pump is ordered

Hot Water Return Line 5/8" OD CU (optional)

Condenser Supply Line 7/8" OD CU on Models BU046WG/BU045WG

1 1/8" OD CU on Models BU071WG/BU070WG

Hot Water Supply 5/8" OD CU (optional)

Monitoring Panel

Condensate Drain 3/4" FPT

Field pitch a min. of 1/8" (3.2mm) per ft. (305mm). Units without a condensate pump have a factory-supplied trap in the unit, so a field trap should not be added. Units with a condensate pump will require a field-supplied trap downstream from the pump. The drain line must comply with all applicable codes. (If condensate pump is ordered piping is out top of unit).

PIPING OUTLET LOCA TIONS

(See Cabinet and Floor Planning

Dimensional Data for Piping

Opening Sizes.)

SL-11898 PG 9

10

Page 16
Image 16
Liebert 3000 installation manual Piping outlet locations through