Installation
Figure 7 Piping connections for chilled water
UPFLOW (BU) MODELS
Piping outlet locations through
the plenum are the same as the unit. See below for descriptions and connectoin sizes
Humidifier Water Supply
Line 1/4" OD CU
Condenser Re turn Line 7/8" OD CU on Models
BU046WG/BU045WG 1 1/8" OD CU on Models
BU071WG/BU070WG
Condensate Pump Line 1/2" OD CU
Used only if optional condensate pump is ordered
Hot Water Return Line 5/8" OD CU (optional)
Condenser Supply Line 7/8" OD CU on Models BU046WG/BU045WG
1 1/8" OD CU on Models BU071WG/BU070WG
Hot Water Supply 5/8" OD CU (optional)
Monitoring Panel
Condensate Drain 3/4" FPT
Field pitch a min. of 1/8" (3.2mm) per ft. (305mm). Units without a condensate pump have a
PIPING OUTLET LOCA TIONS
(See Cabinet and Floor Planning
Dimensional Data for Piping
Opening Sizes.)
10