Liebert 3000 installation manual DPN000209_Rev0, Split System Models

Models: 3000

1 76
Download 76 pages 48.63 Kb
Page 68
Image 68
DPN000209_Rev0

Split System Models

Figure 32 3 ton water/glycol cooled condensing unit (con't.)

Single- or three-phase electric

Field-supplied unit disconnect

switch when optional disconnect

service not by Liebert

is not provided in unit

 

Field-supplied 24V NEC Class 1

 

wiring to fan/coil unit

 

Field-supplied 24V NEC

 

Class 1 wiring to drycooler

 

(glycol-cooled units only)

Earth/ground connection

Connection terminal for field-supplied earth-grounding wire

Factory-wired components

Line voltage electric poweron electric panel supply entrance

Optional factory-installed disconnect switch

Low-voltage electric power supply entrance

Remote drycooler connection

Heat rejection connection.

DPN000209_Rev0

Terminals 70 & 71 supplied for

Field-supplied 24V NEC Class 2 wiring.

 

connection to remote drycooler

 

Wire connections from evaporator mod:

 

Use field-supplied 24V NEC

 

1.

24V GND

 

Class 1 wiring (glycol-cooled

 

2.

24V supply

 

units only)

 

3.

High pressure alarm (opt)

 

 

 

4. Hot gas bypass connection (only on units with hot gas bypass)

NOTES

1.Refer to specification sheet for full load amp. and wire size amp. ratings.

2.Control voltage wiring must be a minimum of 16 GA (1.6mm) for up to 75' (23m) or not to exceed 1 volt drop in control line.

62

Page 68
Image 68