Liebert 3000 installation manual Piping Connections, Dimensional Data

Models: 3000

1 76
Download 76 pages 48.63 Kb
Page 67
Image 67
DIMENSIONAL DATA

Split System Models

Figure 31 2 and 3 ton water/glycol cooled condensing unit

8

7/8" (225mm)

3 7/8" (98mm)

50 1/4" (1276mm)

 

Overall Dimension

48 1/4" (1225mm) Threaded Rod Centers

8 7/16" (214mm)

46 1/2" (1181mm)

Cabinet Dimension

Customer Supplied

 

Threaded Rods for Module

 

Support from Ceiling (typ. 4).

Outlet

 

Inlet

Holes for Module

Rigging (typ. 2 each end).

Integral Hanging Bracket

14" (356mm) Overall Cabinet Dimension

12" (305mm) Threaded Rod Centers

20 3/4" (527mm)

22 1/2" (572mm) Cabinet

Dimension

Minimum Clearance 33" (838mm) This Side for Component Access and Removal.

Note: Unit is Spaced Evenly in

Reference to Threaded Rod Centers.

 

DIMENSIONAL DATA

 

3/4" (19mm) N.P.T. Female

 

Water/GlycolInlet Connection.

3/4" (19mm) N.P.T. Female

7/8" (22mm) Dia.

Water/GlycolOutlet Connection.

Electrical Entrance

for High Voltage

 

 

Connection.

Suction Line

Male Quick

Connect

Liquid Line

Male Quick

Connect

7/8" (22mm) Dia.

PIPING CONNECTIONS

Electrical Entrance

SL-11085 PG 6

for Low Voltage Connection

61

Page 67
Image 67