Liebert 3000 installation manual DPN000226_Rev0

Models: 3000

1 76
Download 76 pages 48.63 Kb
Page 64
Image 64
DPN000226_Rev0

Split System Models

Figure 29 5 ton centrifugal air cooled condensing unit dimensional data (con't.)

Field Supplied Unit Disconnect

Switch when Factory Unit

Disconnect Switch is not Supplied.

Electric service not by Liebert

Optional Factory Installed

Disconnect Switch

AIR COOLED

Line Voltage Electric Power

Connection terminal for field Supply Conduit Voltage supplied earth grounding wireManual background

Removable Access Panels

Field Supplied 24V NEC Class 2 wiring between condensing unit and fan/coil unit

NOTES:

DPN000226_Rev0

Low voltage electric power supply conduit entrance

Heat rejection connection. Field-supplied 24V NEC Class 2 wiring. See Note 2. Wire connections from evaporator module.

1.24V GND

2.24V supply

3.High pressure alarm (optional)

4.Hot gas bypass connection (only on units with hot gas bypass)

1.Refer to specification sheet for full load amp and wire size amp ratings.

2.Control voltage wiring must be a minimum of 16 GA (1.6mm) for up to 75’ (23m) or not to exceed 1 volt drop in control line.

58

Page 64
Image 64
Liebert 3000 installation manual DPN000226_Rev0