Water Cooled Models
4.3.2High Pressure Valve - 350 psig (2413 kPa) System for 3 Ton Units (Metrex Valve) Adjustment
The valve may be adjusted using a 1/8" diameter rod. Turn the adjusting collar nut counterclockwise to raise head pressure; turn it clockwise to lower head pressure. Rotation directions are viewed from top of valve spring housing.
Figure 14 Metrex Valve adjustment
Adjusting collar nut
Table 12 Refrigerant control settings psi (kPa)
Low Pressure | Low Pressure | High Pressure |
Cut Out | Cut In | Cut Out |
|
|
|
20 (137.9) | 65 (448.2) | 360 (2482) |
|
|
|
Manual Flushing
The valve may be flushed by rotating the socket head screw clockwise. This screw must be in the OUT position (counterclockwise) for normal valve operation.
4.3.3Testing Valve Function
When the refrigeration system has been off for approximately
Should the water continue to flow, the valve is either improperly adjusted or the pressure sensing capillary is not properly connected to the condenser.