Figure 6 Piping connections for water/glycol and GLYCOOL units
DOWNFLOW (BF, BE) MODELS
Monitoring Panel
Condensate Drain 3/4” FPT
Field pitch a min. of 1/8" (3.2mm) per ft. (305mm). The drain line must comply
with all applicable codes.
Condenser SupplyLine
7/8" OD CU on Models BF046WG/BF045WG
1 1/8" OD CU on Models BF071WG/BF070WG
Condenser Return Line
7/8" OD CU on Models BF046WG/BF045WG
1 1/8" OD CU on Models BF071WG/BF070WG
HotWater Return
5/8" OD CU (optional)
HumidifierWater SupplyLine
Hot Water Supply
1/4" OD CU | 5/8" OD CU (optional) |
PIPING OUTLET LOCATIONS |
|
(See Cabinet and Floor Planning | |
Dimensional Data for Piping Opening Sizes.) |