Page 40
Image 40
5.5.3Filling the System

Glycol/GLYCOOL Cooled Models

5.5.3Filling the System

Installation of hose bibs at the lowest point of the system is recommended. When filling a glycol sys- tem keep air to a minimum. Air in glycol turns to foam and is difficult and time-consuming to remove. (Anti-foam additives are available and may be considered.) Open all operating systems to the loop.

With the top vent(s) open, fill the system from the bottom of the loop. This will allow the glycol to push the air out of the top of the system, minimizing trapped air. Fill to approximately 80% of calcu- lated capacity. Fill slowly from this point, checking fluid levels until full.

NOTE

For glycol solution preparation and periodic testing, follow manufacturer's recommendations. Do not mix products of different manufacturers.