Liebert 3000 installation manual Single Circuit Shown

Models: 3000

1 76
Download 76 pages 48.63 Kb
Page 31
Image 31
SINGLE CIRCUIT SHOWN

Air Cooled Models

Figure 11 Air cooled, Lee-Temp general arrangement

Inverted Trap * on discharge line to extend abovebase of coil by a minimum of 71/2" (190mm)

Condenser Coil

Piping Assembly* *

Check Valve

Rotalock Valve **

Traps * Every 25 Ft. (7.6m) of rise on Hot Gas Line only

Head Pressure

 

 

Control with

 

1/4" ( 6.4mm)

Integral Check

 

Pressure Relief

Valve

Lee-Temp

Valve * *

 

 

 

Receiver

Sight Glass

 

 

 

 

Evaporator Coil

Liquid Return from Condenser

Expansion Valve

Hot Gas

Bypass

Valve

 

Solenoid Valves

Shutoff

Sight Glass

Valve *

Filter Drier

Liquid Return

Service

Valves

Hot Gas

Bypass

Manual backgroundCheck Valve* *

Hot Gas Discharge

SL-10061 PG 4 SL-10071 PG 4

Sensing Bulb

External Equalizers

Scroll Compressor

SINGLE CIRCUIT SHOWN

FACTORY PIPING

OPTIONAL PIPING

FIELD PIPING

*Components are not supplied by Liebert but are recommended for proper circuit operation and maintenance.

** Components supplied by Liebert

and mustbe field installed.

25

Page 31
Image 31