CoolTherm

Manual / Bedienungsanleitung

3.4Technical data

Housing material:

Operating Temperature range: abs. atmospheric humidity: Air outlet to heat exchanger: Temperature difference across server: Noise level:

Useful load

Chilled water

Effective cooling capacity depending on type:

Feed temperature:

Return temperature:

Aluminium sheet, sheet steel, galvanized and coated

10 °C to 35 °C / 50°F to 95°F

8g / kg maximum

20 to 25°C / 68 to 77°F according to ASHRAE

approx. 15K

55 dB(A) sound pressure at a distance of 1 m

1.000 kg / 2204 pounds

12 KW to 25 / 35)* KW

12°C / 54°F (other temp. upon consultation)

18°C / 64°F

)*21°C/ 69,8°F at 35 kW (Blade application) (other temp. upon consultation)

Max. operating pressure:

10 bar / 145 PSI

Feed/return supply connection:

1“

CoolTherm

01_998_330_0_k

page / Seite 12/83

Page 14
Image 14
Liebert XDK-W user manual Technical data, Chilled water