CoolTherm

Manual / Bedienungsanleitung

Temperature spread, water:

6K

Use of anti-freeze in the chilled water:

upon request

Water connection:

from below

Condensed water connection:

from below

Nominal voltage at cooling capacity:

12 KW, 17 KW, 25 KW200V to 264V / 50Hz / 60 Hz

Max. operating pressure:

10 bar / 145 PSI

3.Description

3.1General function

CoolTherm complies with the conditions of EN 60950

The modular design facilitates the installation of all 19“ equipment of varying depth.

Heat produced by installed equipment (e. g. servers) is reliably removed using the cold water system integrated into the server cabinet. The cooling system is inherently safe because water cannot reach the server area.

The cooling system comprises a high-performance air/water heat exchanger, fans with fan control unit (fan-speed according to heat load) for the ducted supply of air and cold water connection. The air circuit is closed such that no heat (thermal load) is emitted to the environment.

Attention! CoolTherm only works if cold server feed air and heated server outlet air are fully separated.

Height units not in use have to be sealed using blanking panels.

Top view

 

 

 

 

Air duct

 

 

Luftkanal

 

 

WARM

WARM

 

WARM

Server

WARM

 

COLD

Air separation

 

Lufttrennung

 

KALT

 

CoolTherm

01_998_330_0_k

page / Seite 6/83