CoolTherm
Manual / Bedienungsanleitung
CoolTherm 01_998_330_0_k page / Seite 27/83
Initial Commissioning:
- unfix upper and lower transport lock screw
- connection with general power supply
Automatic door opening operates approx. one minute after initialisation of fan
control unit
- see: Manual closing
- Attention:
If in the time of commissioning the power supply is broken, the doors open itself. If you
use the transport lock screws again,
use always both transport lock screws, otherwise the door could be
damaged.
- Adjusting Magnet Plate:
After rack transport and setup check the position of the magnet plates, it could be
necessary to adjust the magnets to the retain plate. Therfore turn both adjusting screws
(A) until the magnets are in a absolute parallel position to the retain plate and the door
remains closed.
The screw position is to be fixed by locking the nut (B) to threaded bushing,
Door opening
switch with LED
(green)
upper and lower
transport-lock
screw
adjusting screw
for upper
magnet plate
adjusting screw
for bottom
magnet plate