25kW-CoolTherm at 3.58m³/h chilled water flow rate

 

40 kW

 

 

 

 

 

 

 

 

35 kW

 

 

 

 

 

20°C supply air temperature 1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22°C supply air temperature 1)

 

30 kW

 

 

 

 

 

25°C supply air temperature 1)

capacity

25 kW

 

 

 

 

 

 

 

20 kW

 

 

 

 

 

 

 

cooling

 

 

 

 

 

 

 

15 kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10 kW

 

 

 

 

 

 

 

 

5 kW

 

 

 

 

 

 

 

 

0 kW

 

 

 

 

 

 

 

 

10,0 °C

12,0 °C

14,0 °C

16,0 °C

18,0 °C

20,0 °C

22,0 °C

24,0 °C

chilled water supply temperature [°C]

9.5Control Standard Factory Settings

start of fan rotation

10°C (start with 75% rotation)

fan speed control

20 – 23°C (75% - 100% rotation)

start of 3-way valve

10°C (start with closed position)

control of 3way valve

16 – 19°C (0 – 100% control water flow rate)

front LED yellow

temperature alarm >26°C or rear door open

front LED red

temperature alarm >26°C and rear door open

automatic door opening

door release at 35°C

Note:

All settings could vary by project.