CoolTherm

Manual / Bedienungsanleitung

Data overview CoolTherm Table B (Hydraulic Data)

effective

total cooling

total cooling

water

water flow

pressure

water

water

cooling

capacity

capacity

content

rate

loss

temperature

temperature

capacity

(at normal

(at full speed

 

 

cabinet

rise

rise

 

operation)

operation /

 

 

 

(at normal

(at full speed

 

 

emergency)

 

 

 

operation)

operation /

 

 

 

 

 

 

 

emergency)

 

 

 

 

 

 

 

 

kw

kw

kw

l

m³/h

bar

K

K

 

 

 

 

 

 

 

 

12

12,5

13,0

5,9

1,79

0,41

6

6,2

 

 

 

 

 

 

 

 

17

17,8

18,4

7,9

2,55

0,62

6

6,2

 

 

 

 

 

 

 

 

25

26

26,8

9,9

3,72

0,58

6

6,2

 

 

 

 

 

 

 

 

35

36

36,8

9,9

3,72

0,58

8,1

8,51

 

 

 

 

 

 

 

 

CoolTherm

01_998_330_0_k

page / Seite 14/83

Page 16
Image 16
Liebert XDK-W user manual Data overview CoolTherm Table B Hydraulic Data