CoolTherm

Manual / Bedienungsanleitung

Step 3: Disconnect supply cable at the fan terminal block (unscrewing 2 screws and remove connector)

Step 4: Undo the four fastening bolts

The fan is installed in the reverse order of removal.

-Tighten the fan fixing bolts.

-Connect the power supply cable to the fan

-Attention: Reconnect earth cable at the sheet steel cover !

-Switch on the the fuse

Dispose of the old fans correctly!

Regularly inspect the heat exchanger (annually)

-Check heat exchanger on air side for soiling and damage.

-Check feed and return for correct function.

-If necessary clean the air side.

-Regularly check odour trap (external) for correct function.

-Heat exchanger can be pulled out for improved cleaning.

-Regularly visually inspect the water circuit for leaks.

CoolTherm

01_998_330_0_k

page / Seite 30/83

Page 32
Image 32
Liebert XDK-W user manual Regularly inspect the heat exchanger annually, Fan is installed in the reverse order of removal