Heat exchanger connection

Chilled water

Chilled water

feed

return

The chilled water pipes should be insulated against condensation and losses using a waterproof insulation.

Insulation thickness : „F“ (9 - 12mm) λ = 0,037 W/mK (10°C)

5.4Condensed water connection

If the CoolTherm is operated below dew point, condensed water may occur. As standard there is a water connection, 5/8“ diameter, in the condensed water tray for drainage.

Preparations for connecting:

Step 1): Remove air duct

Condensat connection

Step 2.)

Remove cap

Step 3.) Connect the nipple with a drain hose 5/8”

Step 4.)

Move and click the nipple with hose into the hole