CoolTherm
Manual / Bedienungsanleitung
CoolTherm 01_998_330_0_k page / Seite 23/83
Heat exchanger connection
The chilled water pipes should be insulated against condensation and losses using a waterproof
insulation.
Insulation thickness : „F“ (9 - 12mm) λ = 0,037 W/mK (10°C)
5.4 Condensed water connection
If the CoolTherm is operated below dew point, condensed water may occur. As standard there is a
water connection, 5/8“ diameter, in the condensed water tray for drainage.
Preparations for connecting:
Chilled water
return
Chilled water
feed
Step 2.)
Remove cap
Step 3.)
Connect the
nipple with a
drain hose
5/8
Step 4.)
Move and
click the nipple
with hose into
the hole
Step 1):
Remove air
duct
Condensat
connection